The air we breathe contains contamination in the form of water vapour and airbone particles.
During the compression process an air compressor concentrates these contaminants and depending on the design and age will even add to the contamination in the form of oil carry over.
Modern air compressors generally have built in aftercoolers that reduce the discharge temperature of the compressed air and with the help of water separators, remove the bulk of liquid water
In some applications this may be sufficient, but the remaining dirt and moisture content suspended in aerosol form, can, if not removed, damage the compressed air system and cause product spoilage.
Ingersoll-Rand refrigeration air dryers are available in 24 models sizes to suit all applications. When installed with compressed air filters they will provide clean compressed air to the classes as prescribed in ISO 8573.1
Refrigerated Air Dryer
Small air dryers
Benefits
Low power consumption
Environmentally friendly refrigerant (R134a)
High operating limits
+ 16 barg maximum operating pressure
+ 50°C maximum ambient temperature
+ 60°C maximum inlet air temperature
Simple to install, quit fit electrical connection
Mounting holes allow installation onto compressor or walls
Superior performance and reliability backed by world-wide Ingersoll-Rand
DryStar Series Specifications
Model |
Nominal Air Flow |
Max. |
Nominal |
Air |
Dimension |
Weight |
3°C dewpoint |
Pressure |
Absorbed |
connection |
(WxDxH) |
(kg) |
m³/min |
cfm |
(barg) |
(kW) |
(inch) |
(mm) |
|
DS002 |
0.2 |
7 |
16 |
0.16 |
3/8 |
445x197x450 |
18 |
DS004 |
0.4 |
14 |
16 |
0.16 |
3/8 |
445x197x450 |
18 |
DS006 |
0.6 |
21 |
16 |
0.19 |
3/8 |
445x197x450 |
20 |
DS009 |
0.9 |
32 |
16 |
0.22 |
1/2 |
530x282x600 |
32 |
DS012 |
1.2 |
42 |
16 |
0.32 |
1/2 |
530x282x600 |
33 |
DS018 |
1.8 |
64 |
16 |
0.47 |
3/4 |
605x352x700 |
46 |
DS024 |
2.4 |
85 |
16 |
0.63 |
3/4 |
605x352x700 |
55 |
DS030 |
2.95 |
104 |
16 |
0.79 |
3/4 |
605x352x700 |
55 |
Medium & Large air dryers
Benefits
Simple, modern design Compact and light weight Designed for efficiency Modular design Reduced risk of leaks Timed-electric drain valve
Electronic controller with integral energy savings and remote control alarm Refrigerant scroll compressors fitted on model TS110 and above
High operating conditions
+ 50°C maximum ambient temperature
+ 60°C maximum inlet air temperature
Totally environmentally refrigerant R407C
DryStar Series Specifications
Model |
Nominal Air Flow |
Max. |
Nominal |
Air |
Dimension |
Weight |
3°C dewpoint |
Pressure |
Absorbed |
connection |
(WxDxH) |
(kg) |
m³/min |
cfm |
(barg) |
(kW) |
(inch) |
(mm) |
|
| TS040 |
4.00 |
141 |
12 |
0.58 |
1 1/2 |
615x791x552 |
65 |
| TS050 |
5.00 |
177 |
12 |
0.96 |
1 1/2 |
615x791x552 |
66 |
| TS060 |
6.00 |
212 |
12 |
0.95 |
1 1/2 |
615x791x552 |
68 |
| TS070 |
7.00 |
247 |
12 |
0.98 |
1 1/2 |
615x791x552 |
70 |
| TS080 |
8.00 |
283 |
12 |
1.23 |
1 1/2 |
615x791x552 |
73 |
| TS110 |
11.0 |
388 |
12 |
1.21 |
2.00 |
920x1015x672 |
140 |
| TS140 |
14.0 |
494 |
12 |
1.49 |
2.00 |
920x1015x672 |
144 |
| TS180 |
18.0 |
636 |
12 |
1.49 |
2.00 |
920x1015x672 |
150 |
| TS220 |
22.0 |
777 |
12 |
2.11 |
DN80 |
1010x1500x1310 |
400 |
| TS270 |
27.0 |
953 |
12 |
2.76 |
DN80 |
1010x1500x1310 |
420 |
| TS370 |
37.0 |
1307 |
12 |
3.19 |
DN80 |
1010x1500x1310 |
450 |
| TS450 |
45.0 |
1589 |
12 |
4.38 |
DN100 |
1010x1500x1310 |
470 |
| TS600 |
60.0 |
2119 |
12 |
5.63 |
DN100 |
1010x1500x1810 |
550 |
| TS770 |
77.0 |
2719 |
12 |
8.57 |
DN100 |
1010x1500x1810 |
580 |
| TS900 |
90.0 |
3178 |
12 |
7.72 |
DN150 |
1010x1500x1810 |
590 |
| TS1100 |
110.0 |
3885 |
12 |
9.93 |
DN150 |
1010x1500x1810 |
660 |
For air flow required is higher than 110 m³/min, please contact us for details
Desiccant Air Dryers
To remove water or vapor water, some type of dryers is required, to reduce the "dewpoint" of the compressed air.The two most common types used today are the Refrigerated and Desiccant dryers.
Refrigerated Air Dryers can reduce the dewpoint of compressed air to only 1°C - 4°C, as condensed water turns to ice at lower temperatures, causing ice blockages and air flow stoppage. For dewpoints downto -40°C or lower, a Desiccant dryer is clearly the preferred solution, because its' "adsorption" principle works on water vapor only.
Capacity range: 0.1 to 842 m³/min
Max. pressure: 10.3 barg
Dewpoint: -40°C as standard, lower as option
Please contact us for details if you need a very high quality compressed air for system.
|